Options
Test buildings with TABS for MPC-performance evaluation — Comparability and system identification
Publisher
IEEE
Date Issued
2016
Author(s)
Abstract
The research project (MPC-Boxes) deals with the design and construction of two test buildings (Test-Boxes), built for the purpose of performance evaluation of a model predictive controller (MPC) in comparison to a standard controller - for heating and cooling via thermally activated building systems (TABS). The paper introduces the experimental environment, investigates the thermo-physical similarity of the two Test-Boxes, and deals with system identification related aspects. A simple third order state space model (SSM) is derived from first principles. This SSM served as a basis for the derivation of a structured SSM which is facilitated for parameter estimation by means of real measurement data. The performance of the structured SSM is validated with different identification data. The cross-validation performance decreases especially for longer validation intervals, however, within the MPC relevant prediction horizon the performance is still acceptable.
Conference
Subjects
building management systems
cooling
heating
performance evaluation
predictive control
Type
info:eu-repo/semantics/conferenceObject
Konferenzbeitrag
Scopus© citations
2
Acquisition Date
Jan 24, 2025
Jan 24, 2025
Views
73
Acquisition Date
Jan 24, 2025
Jan 24, 2025
Downloads
1
Acquisition Date
Jan 24, 2025
Jan 24, 2025